图书馆订阅: Guest
Thermal Sciences 2000. Proceedings of the International Thermal Science Seminar. Volume 2
June, 11-14, 2000, Bled, Slovenia

DOI: 10.1615/ICHMT.2000.TherSieProcVol2


ISBN Print: 978-961-6353-27-4

Abstract of "A TUBE-IN-TUBE WATER/ZEOTROPIC MIXTURE CONDENSER: DESIGNING PROCEDURE AGAINST EXPERIMENTAL DATA"

page 132
DOI: 10.1615/ICHMT.2000.TherSieProcVol2.530
Get accessGet access

摘要

The object of the present paper is related to the design of condensers for the non-azeotropic mixtures of refrigerants. The high temperature glide mixture R-125/236ea at three different compositions (0.30/0.70, 0.46/0.54, 0.64/0.36 by mass) was tested during condensation inside a 2 m long smooth horizontal tube-in-tube exchanger. The superheated vapour entering the tube is first cooled and then condensed against cold water flowing in the annulus. The experimental data, taken at 400 and 750 kg/(m2 s) mass velocity, is used for comparison against the method of Colburn and Drew (1937). It is shown that the above method gives a reasonably good prediction of the heat flux exchanged in the tube.

Begell Digital Portal Begell 数字图书馆 电子图书 期刊 参考文献及会议录 研究收集 订购及政策 Begell House 联系我们 Language English 中文 Русский Português German French Spain