Volumen 27, 2020 Volumen 26, 2019 Volumen 25, 2018 Volumen 24, 2017 Volumen 23, 2016 Volumen 22, 2015 Volumen 21, 2014 Volumen 20, 2013 Volumen 19, 2012 Volumen 18, 2011 Volumen 17, 2010 Volumen 16, 2009 Volumen 15, 2008 Volumen 14, 2007 Volumen 13, 2006 Volumen 12, 2005 Volumen 11, 2004 Volumen 10, 2003 Volumen 9, 2002 Volumen 8, 2001 Volumen 7, 2000 Volumen 6, 1999 Volumen 5, 1998 Volumen 4, 1997 Volumen 3, 1996 Volumen 2, 1995 Volumen 1, 1994

Journal of Enhanced Heat Transfer

DOI: 10.1615/JEnhHeatTransf.v7.i2.30
pages 97-107

Enhanced Effect of a Horizontal Micro-fin Tube for Condensation Heat Transfer with R22 and R410A

Jeong-Tae Kwon
Department of Mechanical Engineering, Hoseo University, Asan, Korea
Su Ki Park
Korea Electric Power Research Institute, Moonji-dong 103-16, Yousoung-gu, Taejon, 305-380, Korea
Moo Hwan Kim
Division of Advanced Nuclear Engineering, POSTECH, Pohang, Gyeongbuk 37673, Republic of Korea; Department of Mechanical Engineering, POSTECH, Pohang, Gyeongbuk 37673, Republic of Korea

ABSTRAKT

This study presents the local heat transfer characteristics of R410A, a potential candidate for replacing R22, condensing in a horizontal smooth and a micro-fin tube. For a comparison, the R22 condensation heat transfer data are also shown.
The test sections of the present experimental apparatus consist of 7 counter-flow heat exchanger type units. The refrigerant flows in a horizontal copper tube and the cooling water flows through the annular space outside of the tube. The in-tube condensation heat transfer coefficients were obtained from the measured overall heat transfer coefficient of each test unit and the annulus-side heat transfer coefficient. The annulus-side heat transfer coefficients were determined from the correlation developed using a modified Wilson plot technique in this study.
The experiment has been conducted with the refrigerant mass flux ranging from 97 to 202 kg/ms. The condensation heat transfer coefficient of R410A in the smooth tube were compared to some existing correlations frequently referred to in open literature. The present data confirmed the applicability of the correlations to this alternative refrigerant for condensation heat transfer in smooth tubes. The enhancement ratio of the micro-fin tube ranged from 1.5 to 2.2 based on the nominal heat transfer area. It becomes higher with decreasing mass flux and increasing quality for both R22 and R410A.