Volume 27, 2020 Volume 26, 2019 Volume 25, 2018 Volume 24, 2017 Volume 23, 2016 Volume 22, 2015 Volume 21, 2014 Volume 20, 2013 Volume 19, 2012 Volume 18, 2011 Volume 17, 2010 Volume 16, 2009 Volume 15, 2008 Volume 14, 2007 Volume 13, 2006 Volume 12, 2005 Volume 11, 2004 Volume 10, 2003 Volume 9, 2002 Volume 8, 2001 Volume 7, 2000 Volume 6, 1999 Volume 5, 1998 Volume 4, 1997 Volume 3, 1996 Volume 2, 1995 Volume 1, 1994

Journal of Enhanced Heat Transfer

DOI: 10.1615/JEnhHeatTransf.v22.i4.20
pages 281-301

SUBCOOLED FLOW BOILING HEAT TRANSFER CHARACTERISTICS OF R134A IN HORIZONTAL HELICALLY COILED TUBES

Lingjian Kong
School of Energy and Power Engineering, Shandong University, Jinan, Shandong Province 250061, China; Energy Research Institute, Qilu University of technology of Shandong Academy Sciences, Jinan, Shandong 250014, PR China
Jitian Han
School of Energy and Power Engineering, Shandong University, Jinan, Shandong Province 250061, China
Changnian Chen
School of Energy and Power Engineering, Shandong University, Jinan, Shandong Province 250061, China
Kewei Xing
The State Key Laboratory of Technologies in Space Cryogenic Propellants, Beijing 100028, China
Gang Lei
The State Key Laboratory of Technologies in Space Cryogenic Propellants, Beijing 100028, China
Ri Li
School of Engineering, University of British Columbia, 1137 Alumni Avenue, Kelowna, British Columbia V1V1V7, Canada

RÉSUMÉ

Subcooled flow boiling heat transfer of R134a in helically coiled tubes was investigated experimentally. Experiments were carried out at pressure ranging from 412 to 653 kPa, inlet subcooled temperature from 5.0 to 11.0° C, heat flux from 0.11 to 15.4 kWm−2 and mass flux from 147 to 249 kg m−2s−1. The wall temperature distribution was analyzed. In the case of single-phase flows, the wall temperature distribution is attributed to the secondary flow and the velocity profile of the main flow. In the case of two-phase flows, the temperature distribution is explained based on the buoyance and drag forces acting on the bubble. An increase of the inlet subcooling leads, for early subcooled boiling, to an increase in the heat transfer coefficient. However, the pressure has an opposite function on heat flux at the onset of nucleate boiling (ONB) and heat transfer coefficient. Besides, raising the mass flux can cause a substantial increase in the heat flux at ONB, but the effect on the heat transfer coefficient was negligible. The correlations of heat flux at ONB and the subcooled boiling heat transfer coefficient in a horizontal, helically coiled tube were developed based on the experimental data.