Journal of Enhanced Heat Transfer
Facteur d'impact: 0.562 Facteur d'impact sur 5 ans: 0.605 SJR: 0.175 SNIP: 0.361 CiteScore™: 0.33

ISSN Imprimer: 1065-5131
ISSN En ligne: 1026-5511

Volumes:
Volume 27, 2020 Volume 26, 2019 Volume 25, 2018 Volume 24, 2017 Volume 23, 2016 Volume 22, 2015 Volume 21, 2014 Volume 20, 2013 Volume 19, 2012 Volume 18, 2011 Volume 17, 2010 Volume 16, 2009 Volume 15, 2008 Volume 14, 2007 Volume 13, 2006 Volume 12, 2005 Volume 11, 2004 Volume 10, 2003 Volume 9, 2002 Volume 8, 2001 Volume 7, 2000 Volume 6, 1999 Volume 5, 1998 Volume 4, 1997 Volume 3, 1996 Volume 2, 1995 Volume 1, 1994

Journal of Enhanced Heat Transfer

DOI: 10.1615/JEnhHeatTransf.2015012442
pages 425-438

PRESSURE DROP IN R-245FA CONDENSATION IN TUBES FITTED WITH COILED-WIRE INSERTS

AJIT KHATUA
Vignana Bharathi Institute of Technology
Parmanand Kumar
Department of Mechanical Engineering, National Institute of Technology, Jamshedpur, India
Hari Narayan Singh
Department of Mechanical Engineering, National Institute of Technology, Jamshedpur, India

RÉSUMÉ

This study examines pressure drop during condensation of R-245fa pure vapor inside two separate horizontal coaxial double-pipe test sections with coiled-wire inserts assembled in series. For each inserted tube and the plain tube, data were collected for mass fluxes in the range of 100 to 250 kg/m2s in increments of 50 kg/m2s for vapor qualities ranging from 0.1 to 0.9. It was observed that the pressure drop inside a horizontal tube is a complex function of vapor quality, mass velocity, and coil pitch, and in a low vapor quality region. The highest pressure drop ratio was 13.33 for a coil pitch of 3.0 mm at a refrigerant mass flux of 150 kg/m2s.