%0 Journal Article
%A Pukhov, A. A.
%A Solov'ev, E. V.
%A Privezentsev, V. V.
%D 2002
%I Begell House
%N 3&4
%P 4
%R 10.1615/HeatTransRes.v33.i3-4.180
%T Investigation of a Thermosyphon Mock-Up Designed to Remove High-Density Heat Fluxes
%U https://www.dl.begellhouse.com/journals/46784ef93dddff27,36643c59749073da,13ffb6435ff3261f.html
%V 33
%X Results of an investigation of a thermosyphon mock-up designed to remove high-density heat fluxes from a lower base are presented. Gas Freon-113 under a pressure of 1 bar was used as a coolant. The model of accelerated separation of vapor conglomerates by liquid streams created as a result of natural convection is realized in the mock-up. The investigation confirmed that this method is promising: the range of the boiling mode expands to the heat transfer boundary with density 10 times higher than the critical value in boiling on a horizontal surface under the conditions of natural convection; high-intensity heat transfer to 9·104 W/(m2·K) takes place over the entire range. These results suggest that the thermosyphon with water as a coolant makes it possible to remove heat fluxes of density more than 15 MW/m2 with intensity over 105 W/(m2·K.).
%8 2002-06-01