Published 12 issues per year
ISSN Print: 1044-5110
ISSN Online: 1936-2684
Indexed in
CHARACTERIZATION OF FIRE SPRINKLER SPRAYS USING PARTICLE IMAGE VELOCIMETRY
ABSTRACT
Although fire sprinklers have been used for over a century for fire suppression, little is known about the character of the spray. Particle image velocimetry was used to measure the droplet velocity near the sprinkler in sprays generated from several typical fire sprinklers. The spray near the sprinkler is essentially radial, with a virtual origin for the spray velocity that is between the orifice and the deflector for pendant sprinklers and between the orifice and 0.05 m above the deflector for upright sprinklers. The maximum radial velocity in the spray ranges from 5.8 to 14.1 m/s, depending on the sprinkler and the pressure in the sprinkler pipe. The spray velocity profiles near sprinklers are dependent on the azimuthal angle and the elevation angle, though not strongly dependent. There is very little difference in the velocity profiles for pendant and upright sprinklers. However, in some cases the measured velocity can be related to sprinkler features such as notches in the deflector. Scaling the radial velocity using the water density and pressure as Ur(ρ/P)1/2 collapses the droplet velocity profiles over a wide range of pressures. The average radial velocity at a distance 20 cm from the sprinkler is approximately 0.6(P/ρ)1/2, while the maximum radial velocity in the spray 20 cm from the sprinkler is 1.0(P/ρ)1/2. The spray velocity profiles reported here are available for use in the National Institute of Standards and Technology's "Fire Dynamics Simulator," a computational model for fires and fire suppression based on large-eddy simulation techniques.
-
Xia J., Luo K., Kumar S., Dynamic Interactions between a Buoyant Reacting Plume and Evaporating Droplets, Fire Safety Science, 9, 2008. Crossref
-
Xia J., Luo K. H., Zhao H., Dynamic Large-Eddy Simulation of Droplet Effects on a Reacting Plume in Countercurrent Configuration, Combustion Science and Technology, 183, 5, 2011. Crossref
-
Santangelo Paolo E., Characterization of high-pressure water-mist sprays: Experimental analysis of droplet size and dispersion, Experimental Thermal and Fluid Science, 34, 8, 2010. Crossref
-
Santangelo Paolo E., Experiments and modeling of discharge characteristics in water-mist sprays generated by pressure-swirl atomizers, Journal of Thermal Science, 21, 6, 2012. Crossref
-
Husted Bjarne Paulsen, Petersson Per, Lund Ivar, Holmstedt Göran, Comparison of PIV and PDA droplet velocity measurement techniques on two high-pressure water mist nozzles, Fire Safety Journal, 44, 8, 2009. Crossref
-
Wu Fan, Cui Yongyi, Qu Fang, Mai Lei, Experimental Study on Fire Extinguishing Characteristics of Automatic Sprinkler System, 2015 Sixth International Conference on Intelligent Systems Design and Engineering Applications (ISDEA), 2015. Crossref
-
Myers T.M., Marshall A.W., A description of the initial fire sprinkler spray, Fire Safety Journal, 84, 2016. Crossref
-
Myers Taylor, Trouvé Arnaud, Marshall Andre, Predicting sprinkler spray dispersion in FireFOAM, Fire Safety Journal, 100, 2018. Crossref