ライブラリ登録: Guest
Thermal Sciences 2004. Proceedings of the ASME - ZSIS International Thermal Science Seminar II
June, 13-16, 2004, Bled, Slovenia

DOI: 10.1615/ICHMT.2004.IntThermSciSemin


ISBN Print: 978-9-61913-930-1

Analysis of loop heat pipe performance under varying wick load

pages 705-709
DOI: 10.1615/ICHMT.2004.IntThermSciSemin.880
Get accessGet access

要約

Loop heat pipes (LHP) are heat transfer devices used to enhance cooling of small spaces and basically consist of sealed tubes connecting a heat source, the evaporator, whose major part is a porous wick, with a condenser that operates as heat sink. In this paper we analyse the effect of curvature of the liquid vapor interface upon the vapor pressure within wick pores. We show how this effect affects start-up by requiring a difference between wick and condenser temperatures as higher as wick pore width becomes smaller. We analysed also transient operation and found that ideally LHP are self-adjusting systems that tend to stable operation. We present a formula to describe the transient regime. The analysis provides also optimization of wick pore width for maximum heat transfer. Optimal pore width is shown to vary with temperature difference between wick and condenser. It is envisaged how this feature may help in LHP design.