AB Pool-boiling experiments investigated the critical heat flux (CHF) for degassed PF-5060 dielectric liquid on inclined and uniformly heated 10×10 mm rough copper (Cu) surfaces. The experiments tested 13 surfaces with average roughness, Ra = 0.039 (smooth-polished), 0.134, 0.21, 0.28, 0.33, 0.58, 0.71, 0.80, 0.925, 1.00, 1.21, 1.44, and 1.79 μm, at inclination angles, θ = 0° (upward facing);
60°, 90° (vertical); and 120°, 150°, 160°, 170°, and 180° (downward facing). In addition, liquid subcooling
in the experiments, ΔTsub, varied from 0 K (saturation) to 30 K. The CHF increased with
increasing both surface roughness and liquid subcooling, but decreased with increasing inclination
angle. For all inclinations, CHFsat on the roughest surface is ~35% higher than on the smoothpolished Cu. Moreover, regardless of Ra, CHFsat values in the downward facing orientation (180°)
are typically ~31% of those in the upward facing orientation (0°). CHF in the upward facing orientation
increases linearly with increasing liquid subcooling at a rate of ~2.2%/K, independent of
Ra. This rate increases with increasing the inclination angle to as much as 4%/K in the downward
facing orientation. The developed CHF correlation based on the present database accounts for surface
roughness and inclination angle, and the liquid's subcooling and physical properties and agrees with
the experimental data to within ±10%.