RT Journal Article ID 7fd615a4602d8f91 A1 Weerts, Benjamin T1 COOLERADO AND MODELING AN APPLICATION OF THE MAISOTSENKO CYCLE JF International Journal of Energy for a Clean Environment JO IJECE YR 2011 FD 2013-05-21 VO 12 IS 2-4 SP 287 OP 307 K1 data centers K1 indirect evaporative cooling K1 economizer K1 PUE K1 energy savings K1 heat exchanger AB The National Snow and Ice Data Center (NSIDC) recently replaced its traditional cooling system with a new air conditioning system that utilizes an economizer and Coolerado air conditioning units. These units represent one of the first commercially available applications of the Maisotsenko Cycle (M-Cycle). A data logging system was installed that measured the data center's power consumption before and after the cooling system was replaced. This data was organized and used to prove a 90% cooling energy reduction for the NSIDC. The data logging system also collected temperatures and humidities of inlet and outlet air of a Coolerado air conditioner. After using these data to validate a theoretical model developed by researchers at the National Renewable Energy Laboratory, the model was used to simulate slightly modified heat and mass exchanger designs of the Coolerado system to improve performance.
Sensitivity analysis was performed and found a few design parameters that are important to the thermodynamic performance of the Coolerado system, while others were proved insignificant. Overall, it was found that the current design performs reasonably well and with minor modifications could perform optimally, as suggested by the theoretical model. PB Begell House LK https://www.dl.begellhouse.com/journals/6d18a859536a7b02,10b176ea48497f3d,7fd615a4602d8f91.html